Full Description
This first edition standard describes 1-in. (25-mm) through 12-in. (300-mm) air valve and vent inflow preventer assemblies designed for use on the outlet of potable water distribution system air valves furnished in accordance with ANSI/AWWA C512 or storage facility vent pipes. The assemblies shall have a minimum design pressure of 25 psig (172.4 kPa [gauge]) and prevent the entry of contaminated water between 0 and 57.7 ft (17.6 m) of submergence andat liquid temperatures ranging from 32F (0C) to a maximum of 12F (52C).
The purpose of this standard is to provide the minimum requirements for inflow preventer assemblies including material, design, inspection, testing, marking, handling, and packaging for shipment.